Skip to main content
Kent Academic Repository

The Performance of Natural Ventilation In A Dance Studio – Lessons From Tracer Gas Measurements And Control Integration

Watkins, Richard, Nikolopoulou, Marialena, Giridharan, R., Kotopouleas, Alkis (2015) The Performance of Natural Ventilation In A Dance Studio – Lessons From Tracer Gas Measurements And Control Integration. In: Proceedings of 31st International PLEA Conference, Passive Low Energy Architecture: Architecture in (R)Evolution. . (KAR id:52520)

PDF (PLEA conference paper 2015 (Bologna, Italy))
Language: English
Download this file
(PDF/1MB)
[thumbnail of PLEA conference paper 2015 (Bologna, Italy)]
Preview
Request a format suitable for use with assistive technology e.g. a screenreader

Abstract

The naturally ventilated, three storey School of Arts Jarman Building provides two dance studios, an exhibition gallery, teaching rooms, video editing suites and offices. The main dance studio is double-height, has underfloor heating and accommodates sixty people. Fresh air enters from low level perimeter louvres and exits at high level through a stack that rises through the third storey to a stack terminal with motorized louvres. Tracer gas (CO2) measurements were used to measure the ventilation rate in conjunction with hot-wire anemometry in the stack tower. The results showed that when all air inlet and exit louvres were set to closed, the residual air flow up the stack was 0.33m3/s representing a potential heat loss of 9kW in winter at 0°C outside. When the louvres were all open, the air flow increased to between 0.49 and 0.62m3/s, a level consistent with the studio’s design occupancy. It was found that the studio’s 4m high perimeter curtains represent a barrier to fresh air entering the main room space and cause the incoming air to migrate upwards towards the stack exit and effectively bypass the central part of the studio. Tracer gas decay rates showed that the main space experienced an air exchange rate 50% less than that for the overall studio. An investigation of the controls also revealed that the underfloor heating system operated independently of the control of the stack ventilation system, leading to simultaneous heating and venting. The research shows the vital importance of prescribing contractually that key controls are integrated, that fresh air dampers are well-sealed when closed, and the importance of designing a fresh air supply that matches the way a space is used.

Item Type: Conference or workshop item (Paper)
Uncontrolled keywords: natural ventilation stack ventilation underfloor heating controls integration tracer gas
Subjects: Q Science
Divisions: Divisions > Division of Arts and Humanities > Kent School of Architecture and Planning
Depositing User: Richard Watkins
Date Deposited: 29 Nov 2015 17:03 UTC
Last Modified: 09 Dec 2022 05:11 UTC
Resource URI: https://kar.kent.ac.uk/id/eprint/52520 (The current URI for this page, for reference purposes)

University of Kent Author Information

  • Depositors only (login required):

Total unique views for this document in KAR since July 2020. For more details click on the image.